SK-460-011 2 I56-3435-002
©2009 Honeywell International Inc.
FIGURE 3. TYPICAL 2-WIRE INITIATING CIRCUIT CONFIGURATION, NFPA STYLE B:
C1074-00
WIRING
NOTE: All wiring must conform to applicable local codes, ordinances, and
regulations. This module is intended for power limited wiring only.
1. Install module wiring in accordance with the job drawings and appropri-
ate wiring diagrams.
2. Set the address on the module per job drawings.
NOTE: Monitor module L (using terminals 6 and 7) responds at the ad-
dress set on the code switches. Monitor module H (using terminals 8 and
9) will automatically respond at the next higher address. For example, if
the code switches are set to 76, module L will respond at address 76 and
module H will respond at address 77. Use caution to avoid duplicate ad-
dressing of modules on the system.
3. Secure module to electrical box (supplied by installer), as shown in
Figure 2.
H
L
TWO INITIATING DEVICE CIRCUITS (L&H), EACH
POWER LIMITED TO 240 mA @ 11 VDC MAX.
UL LISTED CONTACT CLOSURE DEVICES MAY
BE USED. DO NOT MIX FIRE ALARM INITIATING,
SUPERVISORY, OR SECURITY DEVICES ON THE
SAME INITIATING DEVICE CIRCUIT.
INSTALL CONTACT CLOSURE DEVICES PER
MANUFACTURER’S INSTALLATION INSTRUCTIONS.
47k EOL
RESISTOR
ELR-47k
47k EOL
RESISTOR
ELR-47k
TO NEXT
DEVICE
(+)
(−)
(+)
(−)
(+)
(−)
FROM PANEL OR
PREVIOUS DEVICE
CONNECT MODULES TO LISTED
COMPATIBLE CONTROL PANELS ONLY
MONITOR L (TERMINALS 6 & 7) RESPONDS AT ADDRESS
SET ON CODE SWITCHES. MONITOR H (TERMINALS 8 &
9) RESPONDS AT NEXT HIGHER ADDRESS.
SIGNAL LINE CIRCUIT (SLC)
32 VDC MAX. SHIELDED-TWISTED
PAIR IS RECOMMENDED
MONITOR
MODULE
ALL WIRING SHOWN IS
SUPERVISED AND POWER LIMITED