MOUNTING
Mounts directly to 4-inch square electrical boxes (see Figure 2). The box
must have a minimum depth of 2
1
/8 inches. Surface mounted electrical boxes
(SMB500) are available from Silent Knight.
FIGURE 2A. MODULE MOUNTING:
C1075-00
SK-460-011 1 I56-3435-002
SK-Monitor-2 Dual Monitor Module
INSTALLATION AND MAINTENANCE INSTRUCTIONS
BEFORE INSTALLING
This information is included as a quick reference installation guide. Refer to
the control panel installation manual for detailed system information. If the
modules will be installed in an existing operational system, inform the opera-
tor and local authority that the system will be temporarily out of service. Dis-
connect power to the control panel before installing the modules.
NOTICE: This manual should be left with the owner/user of this equipment.
GENERAL DESCRIPTION
The Dual Monitor Module is intended for use in intelligent, two wire systems.
It provides two independent 2-wire initiating device circuits (IDC), at two sep-
arate, consecutive addresses. It is capable of monitoring normally open con-
tact fire alarm and supervisory devices, or either normally open or normally
closed security devices. The module has a single panel controlled red LED.
COMPATIBILITY REQUIREMENTS
To ensure proper operation, this module shall be connected to a compatible
Silent Knight system control panel (list available from Silent Knight).
FIGURE 1. CONTROLS AND INDICATORS:
SPECIFICATIONS
Normal Operating Voltage: 15 to 32 VDC
Maximum Current Draw: 6.4 mA (LED on)
Average Operating Current: 750µA (LED flashing)
Max. SLC wiring Resistance: 40 ohms
EOL Resistance: 47K Ohms
Max. IDC wiring resistance: 1,500 Ohms
Maximum IDC Voltage: 11.7 Volts
Maximum IDC Current: 240µA
Temperature Range: 32˚F to 120˚F (0˚C to 49˚C)
Humidity: 10% to 93% Non-condensing
Dimensions: 4
1
/2˝ H x 4˝ W x 1
1
/4˝ D (Mounts to a 4˝ square by 2
1
/8˝ deep box.)
Accessories: SMB500 Electrical Box
I56-3435-002
12 Clintonville Road, Northford, CT 06472
203.484.7161; Fax: 203.484.7118
www.silentknight.com