System Overview
151253 3
Section 3
System Overview
3.1 Terminal Descriptions and Electrical Ratings
CAUTION
Each output circuit is rated at 3 amps. DO NOT OVERLOAD. Overloading a circuit will cause it to shut
down (power limit). The circuit will automatically reset once you remove the overload condition.
Terminal # Description Ratings
TB1
1 AC (black–“hot”)
120 VAC 60 Hz, 3A2 Earth Ground
3 AC (white–“neutral”)
TB2
1 Auxiliary Power (-)
27.4 VDC 3.0 amps
2 Auxiliary Power (+)
3 Notification 4 Output (-)
27.4 VDC 3.0 amps
4 Notification 4 Output (+) Although each output
5 Notification 3 Output (-)
27.4 VDC 3.0 amps
is rated for 3 amps, the
6 Notification 3 Output (+) total current draw from
7 Notification 2 Output (-)
27.4 VDC 3.0 amps
the 4 outputs and the
8 Notification 2 Output (+) auxiliary power must
9 Notification 1 Output (-)
27.4 VDC 3.0 amps
not exceed 9 amps.
10 Notification 1 Output (+)
11 Normally Closed contact 2.5 A @ 250 VAC
or
2.5 A @ 30 VDC
12 Common
13 Normally Open contact
14 Input 2
9 - 30 VDC15 Input 2 (-)
16 Input 2 (+)
17 Input 1
9 - 30 VDC18 Input 1 (-)
19 Input 1 (+)