Sample Applications
151253 25
Figure 5-5 Each Control NAC Activates Five Output NACs
5.2 Non-Resettable Power Application
The 5499 provides a dedicated 3 A auxiliary power output that you can select as
non-resettable (output is always on). See Section 4.8.4 for setting the auxiliary power.
If you need more than 3 A, wire the inputs as shown in Figure 5-6.
Figure 5-6 Auxiliary Output Wiring for Non-Resettable Power
5499
5499
5499
Local Fire Alarm
Control Panel