Pagina 1 - MODEL 5495

Distributed Power ModuleMODEL 5495Installation andOperations ManualDocument 15116108/12/13 Rev M151161:M ECN 13-0708

Pagina 2

Model 5495 Distributed Power Module Installation Manual6 151161You can select which input controls which output, and which inputs are Class A and Clas

Pagina 3 - Contents

Installation151161 7Section 4InstallationBefore installing the 5495, the AC input must first be wired into the building’s main electrical power throug

Pagina 4

Model 5495 Distributed Power Module Installation Manual8 1511614.2 Wire RoutingTo avoid induced noise (transfer of electrical energy from one wire to

Pagina 5 - Introduction

Installation151161 94.3 Current Requirements (Standby and Alarm)4.3.1 Current Drawn From Host Panel Table 4-1 shows the 5495 current draw requirements

Pagina 6 - UL Requirements

Model 5495 Distributed Power Module Installation Manual10 151161Table 4-2: Battery Calculation WorksheetDeviceNumber of DevicesCurrent per DeviceStand

Pagina 7 - System Overview

Installation151161 114.4 Connecting the 5495 to a Control PanelFigure 4-2 shows the general layout of the 5495 PC board. This section also provides sp

Pagina 8 - 3.2 Signal Input Terminals

Model 5495 Distributed Power Module Installation Manual12 1511614.4.1 Common Trouble Relay The 5495 has a Form C trouble relay built into Terminals 11

Pagina 9 - 151161 5

Installation151161 134.5 Notification Appliance WiringNote:Not all devices can use the sync feature. Be sure to check Appendix A to ensure the device

Pagina 10 - DIP switch settings

Model 5495 Distributed Power Module Installation Manual14 151161pass the added current load from notification appliances.Figure 4-4 Class A Supervise

Pagina 11 - Installation

Installation151161 15Class B Supervised Input CircuitsFigure 4-5 shows Class B supervised wiring from a fire alarm control panel to the 5495.Use an EO

Pagina 13 - 151161 9

Model 5495 Distributed Power Module Installation Manual16 1511614.7 Battery ConnectionUse two 12 VDC, 7 AH gel cell batteries inside the 5495 cabinet.

Pagina 14

Installation151161 174.8 DIP Switch SettingsA 7-position DIP switch on the 5495 board allows you to select the following:• How long the 5495 will wait

Pagina 15 - 151161 11

Model 5495 Distributed Power Module Installation Manual18 1511614.8.1 Selecting the Standard Input/Output ConfigurationsFigure 4-7 and Figure 4-8 show

Pagina 16 - 4.4.1 Common Trouble Relay

Installation151161 194.8.1.1 Input/Output Configurations That Select ANSI Temporal-Coded OutputsThe DIP switch settings marked with an asterisk (*) in

Pagina 17 - 151161 13

Model 5495 Distributed Power Module Installation Manual20 1511614.8.2 Selecting Synchronized Output ConfigurationsThe following sections describe how

Pagina 18 - 14 151161

Installation151161 214.8.2.3 Selecting Synchronized System Sensor ConfigurationsTo select the input/outputs for System Sensor synchronized appliances,

Pagina 19 - 151161 15

Model 5495 Distributed Power Module Installation Manual22 1511614.8.3 Setting the Loss of AC DelayNormal selection for reporting loss of AC is 3 hours

Pagina 20 - 4.7 Battery Connection

Sample Applications151161 23Section 5Sample ApplicationsThe drawings in this section show various 5495 configurations, including “daisy-chaining”.5.1

Pagina 21 - 4.8 DIP Switch Settings

Model 5495 Distributed Power Module Installation Manual24 151161Note:When multiple power supplies are used with one control unit they will not sync wi

Pagina 22

Sample Applications151161 25Figure 5-5 Each Control NAC Activates Five Output NACs5.2 Non-Resettable Power ApplicationThe 5495 provides a dedicated 3

Pagina 23 - Temporal-Coded Outputs

151161 iContentsSection 1Introduction ...

Pagina 24

Model 5495 Distributed Power Module Installation Manual26 1511615.3 Door Holder ApplicationIn a typical door holder application, the door holder power

Pagina 25 - 151161 21

Troubleshooting151161 27Section 6TroubleshootingLight-emitting diodes (LEDs) indicate fault conditions. This section describes the LED states.6.1 LEDs

Pagina 26 - 22 151161

Model 5495 Distributed Power Module Installation Manual28 1511616.2 Trouble ConditionsNote: While Input 1 & 2 are activated, Input 1 & 2 will

Pagina 27 - Sample Applications

Troubleshooting151161 296.3 Earth Fault ResistanceTable 6-1 lists the earth fault resistance detection for each applicable terminal on the FACP.Table

Pagina 28 - 24 151161

Model 5495 Distributed Power Module Installation Manual30 1511616.4 Removing and Replacing the Control PanelThis section provides instruction on how t

Pagina 29 - 151161 25

151161 31Appendix AUL Listed Notification AppliancesFor proper operation, you must use polarized devices with a Model 7628 4.7k ohm EOL resistor on ea

Pagina 30 - 5.3 Door Holder Application

Model 5495 Distributed Power Module Installation Manual32 151161Faraday446 Vibrating Bell 476 Vibrating Bell477 Single Stroke Bell2700 -M. -R, -T, -Y,

Pagina 31 - Troubleshooting

UL Listed Notification Appliances151161 33Faraday(cont.)5510 Strobe5511 Strobe5512 Strobe5516 Strobe5517 Strobe5518 Strobe5519 Strobe5521 4” Square Sy

Pagina 32 - 6.2 Trouble Conditions

Model 5495 Distributed Power Module Installation Manual34 151161FCIS2415-FC StrobeS241575-FC StrobeS2430-FC Strobe130-3117C Mini Horn130-3147C Mini Ho

Pagina 33 - 6.3 Earth Fault Resistance

UL Listed Notification Appliances151161 35FCIP2430W-FC Horn/StrobeP2430K-FC Horn/StrobeP2475-FC Horn/StrobeP2475W-FC Horn/StrobeP2475K-FC Horn/StrobeP

Pagina 34

Model 5495 Distributed Power Module Installation Manualii 1511614.8.4 Setting the Auxiliary Output ...

Pagina 35 - Appendix A

Model 5495 Distributed Power Module Installation Manual36 151161GentexGEC-24-15xxHorn/StrobeGEC-24-30xxHorn/StrobeGEC-24-60xxHorn/StrobeGEC-24-75xxHor

Pagina 36 - 32 151161

UL Listed Notification Appliances151161 37Gentex(cont.)GES24-177xStrobeGES3-24xMulti Candella StrobeGESR-24xMulti Candella StrobeGEH-24xHornST24-30xSt

Pagina 37 - 151161 33

Model 5495 Distributed Power Module Installation Manual38 151161System SensorCHRxChimeCHWxChimeCHSRxx2-Wire Chime/StrobeCHSWxx2-Wire Chime/StrobeHRxxH

Pagina 38 - 34 151161

UL Listed Notification Appliances151161 39System Sensor(cont.)PC4Wxx4-Wire Horn/StrobeP4WHxx4-Wire Horn/Strobe High CandelaPC4WHxx4-Wire Horn/Strobe H

Pagina 39

Model 5495 Distributed Power Module Installation Manual40 151161WheelockAH-12xHornAH-24xHornAH-12WPxHorn WeatherproofAH-24WPxHorn WeatherproofAMT-2415

Pagina 40 - 36 151161

UL Listed Notification Appliances151161 41Wheelock(cont.)CH90-24MCCHxChime/StrobeHS-24xHornHS4-241575WxxHorn/StrobeHS4-24MCWxxHorn/StrobeHS4-24MCWHxxH

Pagina 41 - 151161 37

Model 5495 Distributed Power Module Installation Manual42 151161Wheelock (cont.)RSS-121575WxStrobeRSS-241575WxStrobeRSS-24MCCxStrobeRSS-24MCCRxStrobeR

Pagina 42 - 38 151161

UL Listed Notification Appliances151161 43Wheelock(cont.)RSSWP-24MCWHxStrobe Weatherproof ZRS-MCWHxStrobeZRS-24MCCxStrobeZRS-24MCCHxStrobeMB-G6-24 Mot

Pagina 43

Model 5495 Distributed Power Module Installation Manual44 151161

Pagina 44 - Wheelock

-1 151460Silent Knight Fire Product Warranty and Return PolicyGeneral Terms and Conditions• All new fire products manufactured by Silent Knight have a

Pagina 45 - 151161 41

151161 1Section 1IntroductionThe 5495 is a notification appliance circuit and auxiliary power expander that provides up to 6 amps of filtered, 24 volt

Pagina 46 - 42 151161

-212 Clintonville RoadNorthford, CT 06472USARA Number:___________________Manufacturer Warranties and Limitation of LiabilityManufacturer Warranties. S

Pagina 48 - 44 151161

Silent Knight12 Clintonville RoadNorthford, CT 06472-1610203-484-7161Fax: 203-484-7118www.silentknight.com

Pagina 49 - Advanced Replacement Policy

Model 5495 Distributed Power Module Installation Manual2 151161Section 2UL RequirementsWhen installed in accordance with NFPA 70 and NFPA 72 standards

Pagina 50 - Warn-HL-08-2009.fm

System Overview151161 3Section 3System Overview3.1 Terminal Descriptions and Electrical RatingsCAUTIONEach output circuit is rated at 3 amps. DO NOT

Pagina 51

Model 5495 Distributed Power Module Installation Manual4 1511613.2 Signal Input TerminalsTerminals 14 through 19 are polarized signal input terminals.

Pagina 52

System Overview151161 53.3 Notification Appliance Circuit TerminalsTerminals 3 through 10 are the notification appliance circuit output terminals. Eac