P/N 151071
SD500-AIM Input Module and
SD500-MIM Mini Input Module
Installation Instructions
The following instructions are a quick reference
guide, refer to the control panel installation
manual P/N 151139, 151274, 151280, 151295,
151209, or 151302 for detailed system
information.
Wiring the SD500-AIM / MIM
Note: Installation and wiring of these devices must be done in
accordance with NFPA 72 and local ordinances.
Terminate the wiring as shown in Table 1. See
also Figure 1 or Figure 2
Specifications
Table 2 lists the operating specifications for the
SD500-AIM and the SD500-MIM.
Impedance for Earth Ground Fault is 0 Ω for all
terminals.
Figure 1: Class B Wiring the SD500-AIM & SD500-MIM
Table 1: Wire Connections
SD500-AIM
SD500-MIM
Terminals
To:
FACP or SLC
Loop Terminals
Contact
SLC
SLC
OUT
SC–
+S+
Contact
A out
CLASS A
OR B
To N.O. Contact
B out To N.O. Contact
A IN
CLASS A ONLY
(SD500-AIM Only)
End of Loop A
End of Loop B
B IN
Table 2: SD500-AIM and SD500-MIM Specifications
Specifications
Max. Line resistance 50Ω
Max. Alarm
Current
One device in alarm
23mA. 46 mA for two
devices in alarm.
.5 mA for each addi-
tional device in
alarm.
Max. Voltage 33 V
Operating Temperature 0° to 49° C
(32° to 120° F)
Indoor use only
Table 2: SD500-AIM and SD500-MIM Specifications
Specifications
Alternate
Construction
Vista de pagina 0
1 2

Indice de contenidos

Pagina 1 - Installation Instructions

P/N 151071 SD500-AIM Input Module and SD500-MIM Mini Input Module Installation InstructionsThe following instructions are a quick reference guide, ref

Pagina 2 - Setting the Devices Address

SD500-AIM Input Module and SD500-MIM Mini Input Module Installation Instructions27550 Meridian Circe, Suite 100Maple Grove, MN 55369-4927763-493-6455

Comentarios a estos manuales

Sin comentarios